適用范圍 1 區(qū)、2 區(qū)危險氣體場所; IIA、IIB、IIC 類T1~T4 組性氣體或蒸氣環(huán)境; 戶內(nèi)、戶外(IP54,*IP65)。 Applying scope Hazardous gas areas: Zone 1&2 ; Explosive gas or vapor atmospheres:class IIA、IIB、IIC, temperature class: T1~T4; Indoor and outdoor(IP54,*IP65).
防爆原理 將普通電器元件裝入一個充滿保護(hù)氣體的主腔內(nèi),保證主 腔內(nèi)部保護(hù)氣體的壓力高于外部環(huán)境氣體,以免性混 合物進(jìn)入主腔,或保證足量的保護(hù)氣體通過使內(nèi)部的 性混合物的濃度降至下限以下,從而達(dá)到防爆的目的。 Explosion-protected principle Put normal equipment components into a main chamber which is filled with protective gas to ensure the pressure of the inner protective gas is higher than the outer to pretect explosive mixture from entering main chamber, or to ensure enough quantity of protective gas so that the consistency of explosive mixture is below the explosion limit to achieve the aim of explosion protection.
產(chǎn)品特色 采用主、副盤(柜、箱)結(jié)構(gòu),主盤為正壓腔,內(nèi)裝各種規(guī) 格普通的電器元件和防爆必須的通風(fēng)布?xì)庀到y(tǒng)、檢壓傳 感系統(tǒng)、氣壓調(diào)節(jié)系統(tǒng)等;副盤內(nèi)裝防爆壓力顯示系統(tǒng)、 防爆換氣自控系統(tǒng)、防爆報警系統(tǒng)、防爆電源自切換系 統(tǒng)、進(jìn)出氣源連接口、外部的進(jìn)出電纜密封裝置等 ; 正壓腔內(nèi)可安裝各種普通的檢測儀表、分析儀表、顯示儀 表、監(jiān)視器、微電腦觸摸屏、大功率變頻器等,內(nèi)裝電器 元件基本不受限制 ; 外殼采用優(yōu)質(zhì)碳鋼或不銹鋼板焊接成型,表面高壓靜電 噴塑; 結(jié)構(gòu)形式可為盤式、柜式、箱式、操作臺式; 按進(jìn)氣方式可分為正壓通風(fēng)型和正壓補(bǔ)償型 ; 正壓通風(fēng)型為不間斷連續(xù)供氣,正壓腔內(nèi)電器元件的工 作熱量可隨時帶走,具有良好的散熱功能 ; 正壓補(bǔ)償型為間斷性供氣,正壓腔具有良好的保壓密封 性能 ; 用戶須自給氣源( 凈化空氣或氮氣) ,氣源壓力為 0.4MPa~0.8MPa;通常現(xiàn)場的儀表氣源可滿足要求。 Features It adopts the structure of main switchboard and assistant switchboard. Main switchboard is the pressurized chamber, inside installed the normal components and the needed ventilating system, sense system and air pressure adjustment system; the inside of assistant switchboard installed explosion-protected displaying system, gas exchanging autocontrol system, alarming system, power autoswitch system, in and out gas source joint and the exterior in and out cable sealing device; The pressurized chamber is able to install various common check meters, analysis meter, display meter, monitor, microcomputer feeling screen, high-power transducer and so on. The inside installed components are normally without limit; The shell adopts moulded high-quality carbon steel or stainless steel with pressurized static plastic-sprayed surface; The structure b includes meter panel、tank、box and operation platb; There are pressurized ventilation and pressurized compensation entering types. Pressurized ventilation type is of continuous air feed, and the heat of the components in general cavity can be sent out which provides good heat-disfusing function; Pressurized compensation type is of discontinuous air feed, and it has good pressure guarantee and sealing function; The user must supply gas source (clean air or nitrogen gas),the gas pressure is 0.4MPa~0.8Mpa; usual gas source is available
主要技術(shù)參數(shù): 1、防爆標(biāo)志:Ex pdemIIBT4或pdemIICT6; 2、防護(hù)等級:IP54(*IP65); 3、副盤(柜、箱內(nèi)供電:AC220/230V,50Hz~60Hz,10A; 4、輸入氣源壓力為:0.4MPa~0.8MPa,凈化空氣或氮氣等保護(hù)氣體; 5、進(jìn)氣口:G1/2 6、換氣量:10~20m3/h 7、換氣時間:10~30min(由防爆檢測單位確定,Tp=5×V/Q Tp:換氣時間;V:主腔內(nèi)凈容量,Q:保護(hù)氣體流量; 8、耗氣量:2~8m3/h 9、功能指標(biāo): a、儀表電器供電前,按啟動按鈕對主盤(柜、箱)內(nèi)剩余空氣進(jìn)行自動換氣,換氣結(jié)束自動維持正壓值為150Pa≤P<350Pa,此時可向正壓柜主腔內(nèi)電器供電; b、內(nèi)部正壓值P≥350Pa時,自動系統(tǒng)自動關(guān)閉進(jìn)氣或開啟排氣閥; c、內(nèi)部正壓值P<150Pa時,自動補(bǔ)氣; d、內(nèi)部正壓值P<80Pa時,自動聲光報警; e、內(nèi)部正壓值P<50Pa時,自動切斷電源。
執(zhí)行標(biāo)準(zhǔn) GB3836.1-2000、GB3836.2-2000、GB3836.3-2000、GB3836.5-2004、GB3836.9-200× |