CC0*A 控制輸出裝置
Name Control output isolator card Output isolator card Output isolator card
(4 to 20 mA output) (4 to 20 mA output) (1 to 5 V output)
Model CC0*A CA0*A CH0*A
Input signal 4 to 20 mA DC 1 to 5 V DC
Input resistance (Voltage drop up to 5V) 1 MΩ (100 kΩ when power off)
Output signal 4 to 20 mA DC, 1 point 1 to 5 V DC, 1 point
Output resistance – Up to 1 Ω
Output load resistance Up to 750 Ω 2 kΩ or more
Signal isolation Between b and output signals, b signal and power b, output signal and power
b
Accuracy Within _0.2 % of span Within _0.1 % of span
Effect of ambient temperature change Max. _0.2 % of span for 10 _C change
Effect of power supply voltage change Max. _0.1 % of span for change of 20 to 130 V DC or 80 to 138 V AC
Power Consumption (100 V AC supply) 4.8 VA 5.6 VA 4.4 VA
Current Consumption (24 V DC supply) 75 mA 105 mA 63 mA
Name Input/Output through-card
Model CX1
Card with the b side directly connected to the output side.
Input/Output signal Can be used when a signal from the field side is b directly to a system, or an output signal of the system
is output directly to the field side without insulation. (There is no secondary output on the system side.)
COMMON
The following is specifications common for C Series Signal Conditioner Card.
Common Specifications
Mounting b Mounted in signal conditioner nests (CNC, CNM)
External wiring Connect M4 screw terminals for I/O in the signal conditioner nest
External dimensions 170 (Height) _ 27 (Width) _ 231 (Depth) mm
Weight 300 g
Insulation resistance 100 MΩ at 500 V DC between Input and Output, Input/Output and Power/Ground, or Power and Ground
Withstanding voltage 1000 V AC for 1 minute between Input and Output, Input/Output and Power/Ground, or Power and Ground
Ambient temperature 0 to 50 _C
Ambient humidity 5 to 95 % RH (non-condensing)
AC-DC // AC/DC, each card has power supply circuit inside (except CX1 card)
Power supply voltage DC drive: 20 - 130 V, no polarity
AC drive: 80 - 138 V, 47 - 63 Hz